From civil pump foundations to high-elevation overhead sprinkler grids, our certified mechanical fitters and fire protection engineers execute turnkey installations adhering strictly to NBC 2016 Part 4, IS 1239 / IS 3589 piping standards, and local seismic zone structural bracing requirements.
Trenching, bituminous anti-corrosive coating, holiday testing, and laying of heavy C-Class underground external loop ring mains around the facility perimeter to supply all yard hydrants without single-point failure bottlenecks.
Supply, mounting, alignment, and grouting of main centrifugal electric motor fire pump, standby diesel engine-driven pump with heat exchanger cooling, jockey pump, automatic changeover panel, and vibration isolators.
Vertical riser piping (100mm / 150mm diameter) passing through service shafts, landing valve tie-ins on every floor level, air release valves at the rooftop crest, and external fire brigade pumping inlets at ground grade.
Distribution pipes, cross mains, and branch lines secured with UL/FM certified clevis hangers and anti-sway seismic braces suitable for Uttarakhand Himalayan seismic zones IV and V.
Fire-survival armored twisted-pair 2-core 1.5 sq mm copper cabling (IS 2189) run through heavy-gauge galvanized steel conduits to ensure circuit integrity during emergency fire conditions.
Full system pressurized with water to 15-20 kg/cm² for 24 continuous hours in the presence of client engineers to confirm zero pressure drop, complete joint rigidity, and structural integrity.
Send us your architectural CAD drawings for an accurate bill of quantities (BOQ) and itemized turnkey installation estimate.